Generator switchgears have high demands of availability and personal safety at high current and short circuit loads. They are the interface between your generator and the distribution grid. Our air-insulated, type-tested and factory assembled switchgears for indoor installation fulfil the standard IEC 62271-200.
Your advantages
Our switchgear M6-G in withdrawable unit design is used as high current- and generator switchgear and is applied in power plans and industrial plants. Apart from the generator circuit breakers, distribution circuit breakers according to standard IEC 62271-100 can also be used in the switchgear.
Technical data | |
---|---|
Rated voltage | …17.5kV |
Rated current | …5200A |
Rated short time current 3s | ...63kA |
Rated short time current 1s | …72kA |
Rated peak withstand current | …193kA |
Arc proof withstand current | …72kA |
Loss of service continuity category | ...LSC 2B |
Our medium voltage switchgear M12 in truck type design is primarily used as generator switchgear in gas power plants and hydroelectric power plants. The panels can be configured for different cases of application.
Technical data | |
---|---|
Rated voltage | …17.5kV |
Rated current | …4800A |
Rated short time current 3s | …63kA |
Rated peak withstand current | …173kA |
Arc proof withstand current | …63kA |
Loss of service continuity category | ...LSC 2B |
Our generator switchgear M17 in truck type design is used in most different power plants at very high short-circuit currents.
Technical data | |
---|---|
Rated voltage | …17.5kV |
Rated current | …5400A |
Rated short time current 3s | …72kA |
Rated peak withstand current | …197kA |
Arc proof withstand current | …63kA |
Loss of service continuity category | ...LSC 2B |